The checks that decide whether an assembly can be tested at all, and whether it would protect anything if it were.

Height above the outlets (PVB, SVB)

  • A PVB or SVB must sit at least twelve inches above the highest downstream outlet, measured to the bottom of the assembly.
  • Why: The air inlet has to break the siphon. Below the outlets there is nothing for it to break.

Height above grade (all four)

  • Twelve inches from the floor or grade to the bottom of the assembly is the usual minimum, and thirty inches is the usual maximum to the centre line.
  • Why: Low enough to work on, high enough that the relief port is not sitting in a puddle it can siphon back.

Relief port discharge (RP)

  • An RP relief port discharges to atmosphere through an air gap. It is never directly connected to a drain.
  • Why: A direct connection makes the drain itself the cross-connection you were hired to eliminate.

Never in a pit that can flood (RP)

  • An RP may not go in a pit or vault where the relief port could be submerged.
  • Why: A submerged relief port cannot vent, and it can siphon whatever is in the pit.

Orientation (all four)

  • Fit the assembly the way it is approved. Most are horizontal only, and the approval is for the position as much as the model.
  • Why: A vertical installation of a horizontal-only assembly changes how the poppets seat and voids the approval.

Clearance for testing (all four)

  • Enough room to get a gauge and two hands onto every test cock, and to remove the covers.
  • Why: An assembly that cannot be tested is an assembly that will not be, and it stops being protection the year after it goes in.

Freeze protection (all four)

  • Protect from freezing without blocking access or the relief port.
  • Why: A burst assembly is an open cross-connection, and heat tape wrapped over a relief port is worse than no heat tape.

Approved assembly for the hazard (all four)

  • Confirm the assembly fitted is the one the hazard calls for before you test it.
  • Why: A passing test on the wrong assembly still leaves the water unprotected, and your name is on the report.