Whether a pressure or spill-resistant vacuum breaker passed: the air inlet opening at 1.0 psi or higher and opening fully, and the check at 1.0 psid.

Assembly
Read at the instant the poppet moved
Air inlet once the body drained

Result

PASSED

PVB may be returned to service

Both criteria met. Remember this assembly protects against backsiphonage only, never backpressure.

How it's worked out

Air inlet >= 1.0 psi Check valve >= 1.0 psid

  1. Air inlet opening point1.6 against a 1.0 psi minimum= Pass
  2. Air inlet travelWatched after the body drained= Opened fully
  3. Check valve differential1.9 against a 1.0 psid minimum= Pass