PVB / SVB Pass or Fail
Whether a pressure or spill-resistant vacuum breaker passed: the air inlet opening at 1.0 psi or higher and opening fully, and the check at 1.0 psid.
Result
PASSED
PVB may be returned to service
Both criteria met. Remember this assembly protects against backsiphonage only, never backpressure.
How it's worked out
Air inlet >= 1.0 psi Check valve >= 1.0 psid
- Air inlet opening point1.6 against a 1.0 psi minimum= Pass
- Air inlet travelWatched after the body drained= Opened fully
- Check valve differential1.9 against a 1.0 psid minimum= Pass