Tools
Velocity in the Pipe
The velocity of a flow in a pipe of a given bore, against the usual 8 feet per second design ceiling.
Velocity
4.78 ft/s
A common design ceiling is 8 feet per second in cold water. High velocity through an assembly also lifts the pressure loss across it, which is what starves fixtures downstream.
How it's worked out
V = Q / A, with Q in cubic feet per second
- Pipe areapi x (2.067 / 12)^2 / 4= 0.02330 sq ft
- Convert flow50.0 gpm / 448.831= 0.1114 cu ft/s
- Velocity0.1114 / 0.02330= 4.78 ft/s
The other twenty-three tools
Paperwork
The test
- DC Test WalkthroughStep by step, at the assembly
- RP Test WalkthroughStep by step, at the assembly
- PVB Test WalkthroughStep by step, at the assembly
- SVB Test WalkthroughStep by step, at the assembly
- RP Pass or FailReadings judged against the rule
- DC Pass or FailReadings judged against the rule
- PVB / SVB Pass or FailReadings judged against the rule
- Gauge ElevationCorrecting for where it hangs