Tools
Gauge Elevation
The error a gauge picks up when it is not level with the test cock reference, 0.433 psi a foot, and the reading it should have shown.
Corrected reading
1.03 psid
Corrected from a reading of 1.90 psid
Gauge was not level with the reference point
Gauge sits 2.00 ft below the reference, so it reads high by 0.87 psi. Level the gauge and read it again where you can. This correction is for explaining the error, not for replacing a properly taken reading on a test report.
How it's worked out
Corrected = observed - (reference height - gauge height) x 0.433
- Elevation offset2.00 - 0.00 ft= 2.00 ft
- Convert the water column to pressure2.00 ft x 0.433 psi per ft= 0.87 psi
- Remove the error from the reading1.90 - 0.87= 1.03 psid
The other twenty-three tools
Paperwork
The test
- DC Test WalkthroughStep by step, at the assembly
- RP Test WalkthroughStep by step, at the assembly
- PVB Test WalkthroughStep by step, at the assembly
- SVB Test WalkthroughStep by step, at the assembly
- RP Pass or FailReadings judged against the rule
- DC Pass or FailReadings judged against the rule
- PVB / SVB Pass or FailReadings judged against the rule