The minimum acceptable assembly from the two questions that decide it: how bad the substance is, and whether anything downstream can make its own pressure.

How bad is the substance?
Can anything downstream make its own pressure?
Where does the protection sit?

Minimum assembly

PVB, the pressure vacuum breaker assembly

Acceptable here: PVB, SVB, RP

Pressure vacuum breaker assembly
The minimum
Spill-resistant vacuum breaker assembly
Also acceptable
Reduced pressure principle assembly
Also acceptable

High hazard but no way to generate backpressure. A vacuum breaker is approved here, and it must sit at least twelve inches above the highest downstream outlet to work at all. If anything downstream might ever be pumped, this answer changes to an RP. An air gap is always acceptable and cannot fail mechanically. Where the fixture tolerates losing pressure, it is the better answer. This is the floor, never a permission. The authority having jurisdiction can require more and frequently does.

How it's worked out

The degree of hazard and whether backpressure is possible decide the minimum

  1. Not acceptable: DCA double check is not approved for a health hazard.= Rejected