Expansion Tank

The thermal expansion tank a closed system needs once an assembly is fitted, from the water volume, the two temperatures and the pressures, worked in absolute pressure.

Heater capacity plus what is in the piping
Also the pre-charge the tank needs before it goes on

Minimum tank

1.48 gal

Minimum tank volume

Round up to the next size the supplier stocks, and pre-charge the tank to the supply pressure of 60 psi before it goes on the line. An uncharged tank does nothing.

How it's worked out

Vt = Vs x ((v2 / v1) - 1) / (1 - P1 / P2), pressures absolute

  1. Specific volume cold and hot60 F and 140 F= 0.01603 and 0.01629 cu ft/lb
  2. Expansion factor(0.01629 / 0.01603) - 1= 0.01622
  3. Water that has nowhere to go50.0 gal x 0.01622= 0.811 gal
  4. Convert gauge pressures to absolute60 + 14.7 and 150 + 14.7= 74.7 and 164.7 psia
  5. Acceptance fraction of the tank1 - (74.7 / 164.7)= 0.5464
  6. Tank volume0.811 / 0.5464= 1.48 gal