Parts & Test Cocks
Every component of all four assemblies, what each one does, how it fails, and exactly where each test cock sits on the body.
RP: the parts
How it is built, and how each part fails
| Part | Its job | How it fails |
|---|---|---|
| Number 1 shut-off valve | Isolates the assembly from the supply so a test means something. | Passes water and imitates almost every other fault in this list. Suspect it first, always. |
| Check valve #1 | Holds most of the supply pressure, keeping the zone below it. | Fouled seat or tired rubber, giving a low differential or a leak. |
| Reduced pressure zone | The space the relief valve protects. Its whole purpose is to be lower than the supply. | Not a part that fails, but the thing every reading is about. |
| Differential relief valve | Opens to atmosphere when the zone comes within about two psi of the supply. This is what makes an RP announce its own failure. | Fouled seat, blocked sensing passage, or seized. |
| Check valve #2 | Stops backpressure entering the zone from downstream. | Leaks under backpressure, which shows up as the relief vent dripping a second time after a gauge reset. |
| Number 2 shut-off valve | Isolates the downstream piping. | Passes water, so the downstream side will not come to atmosphere. |
Two independent checks with a zone between them that is kept below the supply pressure, and a relief valve that dumps that zone to atmosphere the moment the margin is lost.
RP: the test cocks
4 test cocks
| Test cock | Where it sits |
|---|---|
| 1 | Upstream of the number 1 shut-off. Supply pressure. |
| 2 | Between the number 1 shut-off and check valve #1. |
| 3 | In the reduced pressure zone, between the two checks. |
| 4 | Downstream of check valve #2, before the number 2 shut-off. |
DC: the parts
How it is built, and how each part fails
| Part | Its job | How it fails |
|---|---|---|
| Check valve #1 | First barrier. Must hold at least 1.0 psid and close drip tight. | Fouling and worn rubber, same as any check. |
| Check valve #2 | Second barrier, independent of the first. | The same, and with no relief valve nobody finds out until the annual test. |
| Bypass meter, detector versions only | Registers small flows, which on a fire line usually means a leak or an unauthorised connection. | Sticks. It only has to move, not to be accurate. |
Two independently acting spring-loaded checks in series, with no relief valve and no way of telling you it has failed. That is exactly why it is not approved for a health hazard.
DC: the test cocks
4 test cocks
| Test cock | Where it sits |
|---|---|
| 1 | Upstream of the number 1 shut-off. Supply pressure. |
| 2 | Between the number 1 shut-off and check valve #1. |
| 3 | Between the two checks. |
| 4 | Downstream of check valve #2, before the number 2 shut-off. |
PVB: the parts
How it is built, and how each part fails
| Part | Its job | How it fails |
|---|---|---|
| Air inlet | Springs open when body pressure falls to about one psi above atmosphere, letting air in to break the siphon. | Fouled, corroded or frozen. Also imitated by a leaking number 1 shut-off. |
| Check valve | Holds against a fall in supply pressure. | The usual fouling and wear. |
| Canopy | Covers the air inlet in service. It comes off for the test. | Left off after a test, which lets debris in. |
One spring-loaded check and one spring-loaded air inlet, fitted above everything it protects. It stops backsiphonage and nothing else.
PVB: the test cocks
2 test cocks
| Test cock | Where it sits |
|---|---|
| 1 | Upstream of the check valve. |
| 2 | Downstream of the check valve, in the body at the air inlet. |
SVB: the parts
How it is built, and how each part fails
| Part | Its job | How it fails |
|---|---|---|
| Vent valve or vent screw | Lets the body down to atmosphere in a controlled way. This is the entire difference from a PVB. | Left open after a test, or the screw not refitted. |
| Air inlet | Same job as on a PVB, tested second here rather than first. | Same as a PVB. |
| Check valve | Same job as on a PVB, tested first here rather than second. | Same as a PVB. |
The same two components as a PVB with a vent valve added, so the body can be brought to atmosphere without discharging water. That makes it usable indoors, which a PVB is not.
SVB: the test cocks
One test cock and a vent
| Test cock | Where it sits |
|---|---|
| 1 | A single test cock upstream of the check valve. |
| Vent | A vent valve or vent screw on the body, used in place of a second test cock. |
The other twenty-three tools
Paperwork
The test
- DC Test WalkthroughStep by step, at the assembly
- RP Test WalkthroughStep by step, at the assembly
- PVB Test WalkthroughStep by step, at the assembly
- SVB Test WalkthroughStep by step, at the assembly
- RP Pass or FailReadings judged against the rule
- DC Pass or FailReadings judged against the rule
- PVB / SVB Pass or FailReadings judged against the rule
- Gauge ElevationCorrecting for where it hangs