Pressure at the Fixture
The pressure left at a fixture once the rise, the loss across the assembly and the piping losses are paid for.
At the fixture
44.3 psi
At the fixture
Take the loss across the assembly from the manufacturer curve for that model and size at this flow. A generic figure will be wrong for the assembly in front of you.
How it's worked out
Residual = supply - elevation - assembly loss - piping loss
- Elevation cost20.0 ft x 0.433= 8.66 psi
- Subtract everything from the supply70.0 - 8.66 - 12.00 - 5.00= 44.3 psi